Product Data ManualHRV600i • HRV700i • HRV1200i • HRV2000i/eHRV2000e
Page 10Airflow Performance DataReduced ReducedESP Low Low Medium Medium High0.00 650 474 734 574 7910.10 635 456 707 569 7640.20 611 447 686 557 7350.
Page 11Airflow Performance DataPH4.12.10.18.06.04.02.00.0wolfriA(cfm) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Fan Pull
Page 12Unit DimensionsHRV600i (with Exhaust Only Defrost)4.000" [102]8.000"[203]8.000"[203]3.535" [90]4.000"[102]28.005"
Page 13Unit DimensionsHRV600i (with Recirculation Defrost)28.120"[714]14.000"[356]4.000" [102]1.750"[44]8.000"[203]2.750"
Page 14Unit DimensionsHRV1200i (with Exhaust Only Defrost)41.206"[1,047]40.326"[1,024]20.000"[508]5.715"[145]20.620"[524]14.2
Page 15Unit DimensionsHRV1200i (with Recirculation Defrost)8.000"[203]1.750"[44]10.000"[254]20.000"[508]2.750"[70]LINE VOLTAG
Page 16Unit DimensionsHRV700i10.000"[254]Center of gravityDirection of airflowHRV700iLBS Kg34 1567 3036 1674 342111.875"[48]EXHAUSTAIROPENIN
Page 17Unit DimensionsHRV2000i14.000" [356]12.750" [324]7.625"[194]10.000"[254]10.000"[254]7.625"[194]5.250"[133]6.
Page 18Unit DimensionsHRV2000eEXHAUST AIROPTIONALSUPPLY AIROUTDOORHOODOUTDOORAIROPTIONALRETURN AIRHEAT RECOVERY COREAND FILTER ACCESSPANELVERTICAL OPE
Page 19Roofcurb DimensionsHRV2000eDETAIL "B"UNITCOUNTER FLASHING(Field Supplied)ROOFING FELT(Field Supplied)UNITBASERAILROOFING MATERIAL(Fie
Table of ContentsPage 2Physical Data - Nomenclature Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Specifications Unit SpecificationsHRV600i, HRV700i, HRV1200iHRV600iHRV700iHRV1200iHP1/41/61/3MCA9.56.614.3MOP12920MotorVoltage120/1/60120
Page 21Controls DataSequence Of OperationBefore start-up, check the unit for obstructive packaging,objects near or in blowers, dampers, etc. Once inst
Page 22Controls DataWall ControlTwo types of remote wall controls are available:1. Standard Wall Control: analog control with slide fan speedswitch an
Page 23OptionsFrost ControlThe requirement for frost control is based upon the outdoorair temperature and humidity content of the return air. In areas
Page 24OptionsDirty Filter SensorThe dirty filter sensor option will monitor thepressure across the filters and will close contactswhen dirt restricts
Page 25OptionsDoor FastenersHRV600i, HRV700i and HRV1200iStandard door access consists of quick release draw latcheswith compression pin hinges for fu
NotesPage 26
Page 27Notes
Venmar CES Inc.Saskatoon, SK Canadawww.venmarces.com© 1999 • PN 206812 • 06/2010
Physical Data - Nomenclature OptionsPage 3INDOOR UNITS OUTDOOR UNITSUNIT NOMENCLATURE OPTIONS 600i 700i 1200i 2000i 2000eFROST CONTROLRecirculation OO
Physical Data - Nomenclature OptionsPage 4INDOOR UNITS OUTDOOR UNITSUNIT NOMENCLATURE OPTIONS 600i 700i 1200i 2000i 2000eHOODSIntake/exhaust hoods ONo
Physical DataPage 5UNIT AIRFLOW TABLE(CFM X 100)Unit 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46HRV600iHRV700iHRV1200iHRV2000i/eFor
Effectiveness Performance DataPage 6HRV600i - POLYPROPYLENE AND ALUMINUM CORESModel Number: PHE500-13.1H-12S-0.11Model Number: AHE500-13.1H-12S-0.14TT
Page 7Effectiveness Performance DataHRV700i - POLYPROPYLENE COREModel Number: PHE500-19H-23S-0.12Type: Plate Nominal Airflow: 400 scfmPressure Drop: 0
Page 8Effectiveness Performance DataHRV1200i - POLYPROPYLENE AND ALUMINUM CORESModel Number: PHE500-13.1H-12S-0.11Model Number: AHE500-13.1H-12S-0.14T
Page 9Effectiveness Performance DataHRV2000i/e - POLYPROPYLENE AND ALUMINUM CORESModel Number: PHE500-15.4H-15.3S-0.11Model Number: AHE500-15.4H-15S-0
Comments to this Manuals