04435 rev. 09READ AND SAVE THESE INSTRUCTIONSINSTALLATION MANUALVB0181VÄNEE2000 HE3000 HEVENMAR1.8 HE2.6 HE
104.4 INSTALLING DUCTWORK AND REGISTERS (CONT'D) 4.4.3 SIMPLIFIED INSTALLATION (VOLUME VENTILATION) (SEE ILLUSTRATION, SECTION 3.3)WARNINGWhen pe
114.5 CONNECTING FLEXIBLE DUCTS TO THE UNIT 4.5.1 FOR MODELS VÄNEE 2000 HE AND VENMAR 1.8 HE Use the following procedure for connecting the insulated
12VO00064.6 INSTALLING EXTERIOR HOODSChoose an appropriate location to install the exterior hoods:• There must be a minimum distance of 6' (1.8
135.1 MAIN CONTROL WITH LCD SCREEN INSTALLATIONWARNINGAlways disconnect the unit before making any connections. Failure in disconnecting power could r
145. INSTALLATION OF THE CONTROLS (CONT'D) 1. Determine the location of the control. NOTE: The wall control must be installed in a central loc
15WARNINGNever connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of
16WARNING• Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.• This product
179.1 WHAT YOU NEED TO BALANCE THE UNIT • A magnehelic gauge capable of measuring 0" to 0.25" water gauge (0 to 62.5 Pa) and 2 plastic tub
189.4 BALANCING PROCEDURE (CONT'D) 4. Move tubing to the other side of the unit (location B in Figure on page 17) and note reading. Adjust the fr
19If the unit does not work properly, reset the unit by unplugging it for one minute and then replug it. If it still not working properly, refer to ta
21. S ERVICE PARTS ...
20PROBLEMS POSSIBLE CAUSES YOU SOULD TRY THIS8The wall control does not work.• TII mode is activated.• The wires may be in reverse position.• The w
3WARNINGIdentifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.!CAUTIONDenotes an inst
41REPLACEMENT PARTS AND REPAIRSIn order to ensure your ventilation unit remains in good working condition, you must use the manufacturer genuine repla
52.1 DIAGRAMS OF AIR FLOWSThe direction of the air flow is indicated in each of the following diagrams (see Figures below).Please note that the stale
63.1 FULLY DUCTED SYSTEM(Primarily for homes with radiant hot water or electric baseboard heating. See Figure at right.)Moist, stale air is exhausted
7WARNINGWhen applicable local regulations comprise more restrictive installation and/or certification requirements, the aforementioned requirements pr
84.3 CALCULATING DUCT SIZE (CONT'D) 4.3.1 EXAMPLE OF CALCULATION: Problem: My installation requires two exhaust registers (one for the kitchen,
94.4 INSTALLING DUCTWORK AND REGISTERS (CONT'D) 4.4.1 FULLY DUCTED SYSTEM (AS ILLUSTRATED IN SECTION 3.1) (CONT'D) Fresh air distribution d