Venmar HRV 2600* Specifications

Browse online or download Specifications for Unknown Venmar HRV 2600*. Venmar HRV 2600* Specifications User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Recovery Ventilators

20LCi and w20LCiHeat and EnergyRecovery VentilatorsInstallation, Operation and Service InstructionsHRV 20LCiERV w20LCiVB0036VB003709/00 0462

Page 2 - Contents

Page 10To access the cassette drive area, loosen the leftside 1/4" x 3/4" (6 x 19mm) socket head cap screwsand remove the bottom left casset

Page 3 - 3 Installation

Page 11Appendix AEquipment DataHRV 20LCi ERV w20LCiShipping weight 750 lbs (341 kg) 725 lbs (330 kg)Net weight 700 lbs (318 kg) 700 lbs (318 kg)Shippi

Page 4 - 3.3 Ductwork Information

Page 12Appendix BTypical Installation and Minimum Distance RequirementsBalancingDamperFlowMeasuringStationBackdraftDamperEXHAUST OUTSIDESUPPLY TO SPAC

Page 5 - :::: : ::

Page 13Appendix DHRV 20LCi Dimensions14.000"[356]12.750"[324]7.625"[194]10.000"[254]10.000"[254]7.625"[194]5.250"[1

Page 6 - 4 Start Up

Page 14Appendix EERV w20LCi DimensionsDimensions in [ ] are in millimetersCenter of gravityLine power supply knockoutDirection of airflowPTSABCADTOTA

Page 7 - Support Wires

Page 15Appendix FEnthalpy Wheel Pressure Drop Chart for ERV w20LCi RotorAppendix GAirflow Performances0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 HPRPM BHP

Page 8 - 5.2 Annual Maintenance

Page 16Appendix HWallControlCONTROL CONTACTSCLASS 2 VOLTAGEWALL CONTROLBLACK1234567891011121314151617181920NOTE: Connections are all dry contacts ex

Page 9 - Figure 3: Cassette and Drive

Page 17Appendix H ContinuedTerminal Control DiagramsRemote fan control can be achieved by connectingdry contact controls to the terminal interface att

Page 10 - See Appendix I for more

Page 18Appendix IWiring Diagram for HRV 20LCi and ERV w20LCi (1 speed, exhaust defrost)SUPPLYMOTORL1 L2 G W/Y BK/YNOTE 3T4 1 2 3

Page 11 - Appendix A

Page 19Appendix I ContinuedWiring Diagram for HRV 20LCi and ERV w20LCi (2 speeds, exhaust defrost)BK/YJ1 6J1 4DEF DAMPERMOTORC O N G/R BK/RSUP

Page 12 - Appendix C

Page 2Contents1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 General Specifications

Page 13 - Appendix D

Page 20Appendix I ContinuedWiring Diagram for HRV 20LCi and ERV w20LCi (1 speed, recirculation defrost)DEF DAMPERMOTORC O N G/R BK/RRECIRC. DAMP

Page 14 - Appendix E

Page 21Appendix I ContinuedWiring Diagram for HRV 20LCi and ERV w20LCi (2 speeds, recirculation defrost)DEF DAMPERMOTORC O N G/R BK/RSUPPLY DAMP

Page 15 - Appendix G

Page 22Problem Cause SolutionUnit will not turn on. Occupied timer contacts open. Check external wiring.Check the wiring in the control box.Check the

Page 16 - Appendix H

Page 31 Safety ConsiderationsHazards may exist within this equipment because itcontains electrical and powerful moving components.Only qualified serv

Page 17 - Appendix H Continued

Page 43.2 Mount UnitLocationMaintain clearance around and above the unit toprovide proper airflow and service access. The freshair intake hood must b

Page 18 - Appendix I

Page 53.4 Install Drain Line For Condensate (For HRV 20LCi unit only)This unit requires a drain line because condensateoccurs during heating seasons.

Page 19 - Appendix I Continued

Page 63.6 Make Electrical ConnectionsElecrical requirementsLocation of wire connections required are shown inAppendix D and E. Units are available in

Page 20

Page 7Unit check points:___ Power connected, no ventilation call - Both fansare off, defrost damper (if equipped) closes offfresh air from outside.___

Page 21

Page 8ERV Exhaust Filter Service (w20LCi)To remove the exhaust filters in the ERV w20LCi,remove the screw holding the filter access door andslide the

Page 22 - Appendix J

Page 95.3 Testing And Replacement Of TheDamper Actuator (ERV only)After disconnecting the power from the unit, determineif the damper is defective. D

Comments to this Manuals