Plenum Supply or Exhaust Fan and Motor
To remove plenum fan and motor disconnect the four-wire
electrical cable from the motor junction box. Remove the
four bolts (#1, Figure 4) and slide the motor and plenum
fan past the inlet cone, then lift out of the unit. A 1¾”
socket is required to remove the fan from the motor shaft.
Both motor shaft and fan bore must be completely free
of paint, grease, oil and dirt. If necessary, clean the sur-
faces with non petroleum based solvent, such as isopropyl
alcohol. Insert the bushing into the fan, making sure the
mating hub is flush against the shoulder at the flats. Posi-
tion the assembly at the desired location on the motor
shaft and hand tighten nut (clockwise) until the assembly
becomes snug on the shaft.
Using a torque wrench and a 1¾” socket, tighten the
nut to the proper installation torque. See table below for
torque value.
Fan should overlap inlet cone by 3/8” [9 mm] and have a
clearance of 1/16” [1.6 mm]. Motor/fan assembly position
is adjustable by loosening the four bolts (#2, Figure 4) and
sliding shelf forwards and back.
Supply FANWALL
®
Array
FANWALL array of multiple direct driven plenum fan and
motor “cubes” are equipped with permanently sealed
bearings and do not require lubrication.
To remove the supply FANWALL and motor, follow the
steps outlined below:
1. Disconnect power to the fan/control panel before main-
tenance. Follow all lockout and tag out procedures.
2. Disconnect the four-wire electrical cable from the
motor junction box. Make note of wire locations for
reinstallation later.
3. Mark motor pedestal location on the motor pedestal
mounting angles (both sides), then loosen and re-
move (four) ½” pedestal bolts that retain the motor
pedestal to the mounting angles (see Figure 6).
Figure 4: Plenum fan and motor
IMPORTANT
No lubrication is necessary during servicing.
CAUTION
Do not hammer or use any type of impact to force the
bushing along the shaft.
CAUTION
The shaft must fully engage the shaft gripping area of
the bushing.
Table 2: Installation Torque Value
Shaft Size Ft-lb
5/8” to ¾” 100
13/16” to 1” 125
1-1/16” to 1¼“ 167
!
WARNING
Disconnect the main power switch to the unit before per-
forming service and maintenance procedures.
Figure 5: FANWALL and motor
VCES-VHC72-IOM-1H