Appendix C: Water Source Heat Pump (WSHP)
Water Line Piping Requirements and Options
Water Supply and Return Piping Requirements
Recommended and required WSHP water line piping com-
ponents with a detailed functional description are outlined
below:
Manual shut-off valves in supply and return water
lines are recommended for isolation and service.
Pressure and temperature gauge connections in the
supply and return water lines are recommended for
testing and service.
A water strainer (16–20 mesh minimum) in the sup-
ply water line is recommended on open loop systems
to eliminate contaminants.
Air vents are required on the high side of the water
supply or inlet line to discharge the non-condensable
air in order to avoid unexpected high head pressure
and poor cooling/heating performance. Manual air
vents are factory installed on the water condenser
and economizer coil (if equipped).
A balancing valve with pressure and temperature
gauge connections in the return water lines is recom-
mended for balancing and service.
A two-way motorized on/off water shut-off valve
is recommended to isolate water flowing through
both the economizer coil (if equipped) and water-to-
refrigerant condenser for conservation when the unit
is off. The motorized water valve must open 90 sec-
onds prior to compressor start-up and remain open
five seconds after the compressor is shut off.
A waterside economizer coil, a three-way modulating
water economizer valve and a temperature sensor
on the water inlet or supply line and downstream of
the economizer coil is required for energy conserva-
tion. The water temperature sensor is input to the
DDC Control System which determines when to
divert water to the economizer coil for energy con-
servation in cooling mode. The three-way motorized
economizer valve and the inlet water temperature
sensor are included with the WSHP WiSE coil option
and factory provided and installed in the compressor
compartment.
A three-way modulating head pressure control valve
is required to maintain stable operation of the re-
frigeration systems when operated on ground loop
water systems when the design inlet water tempera-
ture is below 65°F [18°C] in the cooling mode. A
refrigerant pressure transducer on the compressor
discharge is used to modulate the water flow to the
condenser using a 2 to 10 VDC signal to prevent the
compressor discharge pressure from falling below the
compressor operating limit. The three-way motorized
valve and the pressure sensor option is factory pro-
vided and installed in the compressor compartment
if the design inlet water temperature is below 65°F
[18°C] in the cooling mode.
A flow switch is required on the water return or leav-
ing side of the condenser to monitor the presence or
absence of flow which will shut down the compres-
sor and unit if no flow is present. The water flow
switch option is factory provided and installed in the
compressor compartment.
A water temperature sensor is required on the water
return or leaving side of the condenser to monitor
the water temperature which will shut down the
compressor and unit for freeze protection if the leav-
ing water temperature drops below 35°F [2°C]. The
water temperature sensor option is factory provided
and installed in the compressor compartment on
100% water systems.
A relief valve must be installed in the water supply or
inlet line if the maximum pressure of components is
less than the water supply pressure to prevent dam-
age, injury or death due to instantaneous release of
high pressure water.
Factory Installed Piping Options and
Physical Description
Some of the recommended and required components in
the water supply and return line are available or included
as factory installed and pre-wired options. When the fac-
tory installed options are selected the piping schematic,
component size and C
v
rating will be included based on
compressor selected with the submittals. These compo-
nents are mounted inside the compressor compartment,
piped in copper lines with sweat or threaded connections
as indicated in the submittals. Physical description, opera-
IMPORTANT
WSHP external water supply and return piping shall be in
accordance with National and Local Codes. Line sizing,
pressure limiting devices, backflow preventers, strainers,
valves, flow temperature and pressure measuring, freeze
protection, all other safety or control piping requirements
for system operation are the sole responsibility of the
Installing Contractor and/or Design Engineer. The water
supply must be sized for the minimum flow as indicated
on the mechanical drawings.
!
WARNING
Prior to connection of water supply or inlet line, verify
water pressure is less than the maximum pressure for
components in the water line. To prevent injury or death
due to instantaneous release of high pressure water,
relief valves must be installed in system water supply or
inlet piping.